2.1All calculations must show the formulae.
2.2Substitution of values must be done correctly.
2.3All answers MUST contain the correct unit to be considered.
2.4Alternative methods must be considered, provided that the correct answer is obtained.
2.5Where an incorrect answer could be carried over to the next step, the first answer will be deemed incorrect. However, should the incorrect answer be carried over correctly, the marker has to re calculate the
Q1โ Section header โ
1.1(1\
1.2(1\
1.3(1\
1.4(1\
1.5(1\
1.6(1\
1.7(1\
1.8(1\
1.9(1\
1.10(1\
1.11(1\
1.12(1\
1.13(1\
1.14(1\
1.15(1\ [15] Electrical Technology: Power Systems DBE/May/June 202 SC/NSC15
2.1It is an unsafe act. (1\
2.2Any person who employs or provides work for any person and remunerates that person. (2\
2.3It is when an attempt is made to numerically determine the probability of various adverse events and the likely extent of the losses if a particular event tak es place. (2\
2.4Human rights ensure that human dignity is not infringed and that everyone is treated with respect, have equal opportunities and are not exploited in the workplace. (2\
2.5When the employee feels personally responsible for his/her job performance, he/she shows up on time, puts in his/her best effort and completes projects to the best of his/her ability keeping production high.
3.1.1Impedance is the total opposition to the flow of current in an AC circuit comprising of resistance and reactance. (2\
3.1.2Resonant frequency is a specific frequency at which inductive reactance is equal to the capacitive reactance. (2\
3.1.3In a parallel RLC circuit at resonance the impedance is maximum and current minimum. (2\
3.23. .1 The current through the inductor lags the voltage across it. (1\ 3. .2 (3\
3.2.3(3\
3.2.4(3\
3.2.5(3\
3.2.6(3\ Electrical Technology: Power Systems DBE/May/June 202 SC/NSC Marking Guidelines Copyright reserved
3.3(4\
3.4.1(3\
3.4.2(3\
3.4.3(3\ [35] 310,76 V35
4.1Hydro power generation. Wind power generation. Solar power generation.
4.2Two voltages are available, namely and PH For the same power rating, three phase motors are cheaper, more efficient,
4.3Less current drawn from the supply. Cost saving from drawing less current. Less heat is generated. Maintenance is reduced due to the motor operating cooler. Longer life span of the load.
4.4A three phase supply is generated when three coils are placed 120 apart and
4.5.1(3\
4.5.2(3\ 4. .3 OR (3\ Electrical Technology: Power Systems
4.5.4OR (3\ 4. 4. .1 The product of the two instruments will provide the
4.6.24. .3 A wattmeter measures the electrical power consumed by an application.
4.6.4Zero Amperes (1\
4.7Low power factor increases the total current for a given power, increases the resistance losses and therefore decreases the efficiency of both apparatus and supply systems. Limits the output of both generators and transformers.
4.8.1Power factor meter (1\
4.8.2Voltage transformer. Current transformer. (2\
4.8.3An addition of inductive loads to the system will decrease the reading displayed on the instrument. (1\ [35] Electrical Technology: Power Systems DBE/May/June 20235
5.1Transformation is the way in which transformers increases voltage from a low to a high voltage or decreases voltage from a high voltage to a low voltage. (2\
5.2.1FIGURE ore type FIGURE B Shell type (2\
5.2.2An iron core is needed to provide a magnetic field path to concentrate the magnetic field lines within the core material for maximum induction and power transfer to the secondary windings (2\
5.3Oil forced; Water forced (OFWF\ Oil forced; Air forced (OFAF\ Oil Natural; Air Natural (ONAN\ Oil Natural; Air forced (ONAF\ Oil forced; Air Natural (OFAN\ (2\
5.4Size Frequency Windings ratio Voltage Power factor Efficiency (2\
5.5.1(3\ 5. .2 (3\ 5. .3 OR
5.5.4(3\
5.5.5(3\
5.6.1Using three transformers is bulky or more expensive. (1\
5.6.2Single phase transformers connected in a star delta configuration are used as step down transformer
5.6.3To be able to match the incoming power and to transform the incoming voltage level needed in the correct phas sequence or polarity.
6.1In a three phase motor, induction refers to the process where a rotating magnetic field created by the stator windings induces an emf in the rotor
6.2.1Full load speed is the speed at which the rotor rotates when maximum load is connected to the motor shaft. 6.
6.3Check if the: Shaft rotates freely. Bearings turn smoothly when the shaft is turned. Bearing housings are free from excess grease or dust. (2\
6.4.1(3\
6.4.2OR (3\ Electrical Technology: Power Systems 12 DBE/May/June 202 SC/NSC Marking Guidelines
6.4.3(3\
6.5NOTE: If a learner redrew the diagram as given and swop the labels of L and L
6.6.1N/C Timer normally closed contact (1\
6.6.2MC N/C is used as a normally closed interlocking contact ensuring the star contactor MC gets energised when the start button is pressed and de
6.6.3To reduce the starting voltage. To reduce starting current by 1/3 of delta current To ensure that there is safe transition when switching from star to delta. To protect the wiring in the circuit from burning
6.6.4When the start button is pressed MC energise which closes MC N/O and latches MC
7.1Relays require regular maintenance and repair. Uses much more energy. It requires a lot of space to be wired. It has slower response time. When a single relay develops faults in a panel, it takes much time to locate and
7.2Detection and positioning of objects Measuring rotating speed Counting objects on a conveyer Dete cting direction (2\
7.3Soft wired systems are cheaper when modifications to the system are made Instead of buying new devices, the program is simply altered. (2\
7.4Transistor (1\
7.5A hard wired contactor is a high current device with additionally connected auxiliary contacts used to switch high current devices on the output of a PLC unit to drive the load. A soft wired contactor as used within the software program of the PLC is a virtual